System Overview
Pegasus 2 is a remotely managed PRV control system offering time-based and flow-based pressure modulation to reduce leakage and burst frequency.
Control Features
-
Time-based control – up to 96 settings per day, 7 days per week
-
Flow-based control with override
-
Combined time and flow modulation
-
Optional closed-loop control
-
Configurable fail-safe mode
-
3 solenoid outputs (1 latching + 2 pulsed)
Sensor Inputs
-
2 digital pulse inputs (uni/bi-directional)
-
2 analogue inputs (internal pressure / external pressure / 4–20 mA)
-
Pressure range: 0–20 bar (10 bar calibration standard)
-
Accuracy: ±0.1%
Logging & Monitoring
-
Variable logging rate: 1 second to 24 hours
-
Fast transient logging up to 25 Hz
-
16 alarms per logger
-
Memory: 179,760 readings
-
Top chamber pressure and solenoid activity monitoring
Communication
-
2G / 3G / 4G / LTE-M / NB-IoT
-
Remote configuration via PressView Cloud
-
RS232 / USB programming interface
Mechanical Specifications
-
Dimensions: 315 × 153 × 87 mm
-
Weight: approx. 3.5 kg
-
Protection: IP68 fully submersible
-
Operating temperature: -20°C to +60°C
-
Power: Lithium-thionyl chloride battery (~5 years typical)